[ Table 9-2 : Battery Operation General Events List ]
WEB Display
HMI Display
Description
Measures
Power reset of the system is required.
If the symptom still occurs after reset, repair
of BMS or PCS Control Board is necessary.
BAT5 Additional
Protection
BAT5 ADD P
B48P
When the maximum cell temperature is
above protection level, thus terminating the
system. Automatically returns to normal when
the maximum cell temperature goes below
the limit value.
BAT5 Cell Over Temp
Protection
BAT5 CEL OT
P
B46P
When the minimum cell or rack voltage is
below protection level, thus terminating the
system. Automatically returns to normal when
the minimum cell or rack voltage goes above
the limit value.
BAT5 Cell or Rack
Under Voltage
Protection
BAT5 CEL UV
P
B45P
Power reset of the system is required. If the
symptom persists after reset, replace the
cable connecting the Battery pack and the
INVERTER. After replacement, repair of BMS
or PCS Control Board is necessary.
BAT5 Communication
Protection
BAT5 COM P
B47P
Problem Confirmation
I
96