39
I
Electrical Connections
[ Figure 5-18 : Battery Pack Switch ]
[ Figure 5-17 : Ground Location of Grid and Load ]
6. Change the switch on.
Move
the switch.
5.6.4 Battery Connection Method
To connect the Battery, you need 3 connections :
Ground, (+) and (-). In any case, connection of the INVERTER to ground is mandatory.
To connect the Battery, insert the cable into the INVERTER through the Battery cable gland.
Strip 9 mm of cable from the cable to connect to Load. Connect the Battery cable to the Filter Board CN401.
After lifting the handle of connector, insert the cable and lower the handle of the connector to secure the
Battery cable. Be sure to use the correct size cable and be cables are not loose.
As shown in [Figure 5-17], use the ring terminal to connect the ground wire to the correct location.
[ Figure 5-16 : Power Cable Connection to the Load Connector ]
Battery
Load Grid
Switch
Switch