5.6.3 Load Connection Method
To connect the Load of the INVERTER, you need 3 connections :
Ground, Neutral and Phase. In any case, connection of the INVERTER to ground is mandatory.
To connect the Load output, insert the cable into the INVERTER through the Load cable gland.
Strip 9 mm of cable from the cable to connect to Load. Connect the Load cable to the Filter Board CN603.
After lifting the handle of connector, insert the cable and lower the handle of the connector to secure the
Load cable. Be sure to use the correct size cable and be cables are not loose.
Electrical Connections
I
38
5.6.2 Grid Connection Method
To connect the Grid of the INVERTER, you need 3 connections :
Ground, Neutral and Phase. In any case, connection of the INVERTER to ground is mandatory.
Insert the Grid cable into the INVERTER through the AC cable gland. Strip 9 mm of cable from the cable
to connect to the Grid. Connect the Grid cable to the Sub Filter Board CN1. And then raise the handle
of the connector, insert the cable, and then lower the handle of the connector to secure the Grid cable.
Be sure to use the correct size cable and be cables are not loose.
[ Figure 5-14 : Power Cable Connection to the AC Connector ]
[ Figure 5-15 : Power Cable Connection to the Load Connector ]