4.5.3 DNP Port Configuration Errors
Error Code
Name
Description
212
Invalid DNP address
The DNP address specified in the configuration is
not valid (0 to 65534).
213
Invalid DNP port baud rate
The baud rate code specified in the configuration is
not valid.
219
Invalid DNP data link layer
confirm mode
The data link confirmation mode code is not valid
in the configuration.
220
Invalid DNP data link confirm
time-out
The data link time-out period specified in the
configuration is 0. It must be an integer in the
range of 1 to 65535.
222
Invalid DNP select/operate
arm time duration
The select/operate arm timer is set to 0. It must be
an integer in the range of 1 to 65535.
223
Invalid DNP application layer
confirm time- out
The application layer confirm time-out value is set
to 0. It must be an integer in the range of 1 to
65535.
224
Invalid DNP write time interval
The write time interval is not in the data range in
the configuration. The value must be in the range
of 0 to 1440.
225
Invalid DNP unsolicited
response mode
The unsolicited response mode code is not valid in
the configuration.
226
Invalid DNP unsolicited
response minimum quantity for
Class 1
The unsolicited response minimum quantity for
Class 1 is not valid in the configuration. Value must
be an integer in the range of 1 to 255.
227
Invalid DNP unsolicited
response minimum quantity for
Class 2
The unsolicited response minimum quantity for
Class 2 is not valid in the configuration. Value must
be an integer in the range of 1 to 255.
228
Invalid DNP unsolicited
response minimum quantity for
Class 3
The unsolicited response minimum quantity for
Class 3 is not valid in the configuration. Value must
be an integer in the range of 1 to 255.
230
Invalid DNP unsolicited
response destination address
The unsolicited response destination address is
not valid in the configuration. Value must be in the
range of 1 to 65534.