MVI56-DNP
♦
ControlLogix Platform
Configuring the MVI56-DNP Module
DNP 3.0 Server
User Manual
ProSoft Technology, Inc.
Page 39 of 171
July 21, 2011
[Section]/Item Range
Description
Counters: 0
to
250
points
Number of counter points to configure in the DNP slave device. Each
point will occupy a two word area in the module memory. This number
corresponds to the number of frozen counters. The application maps the
counters to the frozen counters directly.
PLC Counters:
0 to 250
points
Number of counter points configured above that are to be obtained from
the ControlLogix processor. All other counter points must come from the
attached IED units.
Binary Outputs:
0 to 8000
points
Number of digital output points to configure in the DNP slave device.
Each point will be stored as a single bit in the module memory.
PLC Binary Outputs:
0 to 8000
points
Number of digital output points configured above that are to be sent to
the ControlLogix processor. All other binary output points will be sent to
the attached IED units.
Analog Outputs:
0 to 500
points
Number of analog output points to configure in the DNP slave device.
Each point will occupy a one word area in the module memory.
PLC Analog Outputs:
0 to 500
points
Number of analog output points configured above that are to be sent to
the ControlLogix processor. All other analog output points will be sent to
the attached IED units.
Float Outputs:
0 to 250
points
Number of floating-point output points to configure in the DNP slave
device. Each point will occupy a two- word area in the module memory.
PLC Float Outputs:
0 to 250
points
Number of floating-point output points configured above that are to be
sent to the ControlLogix.
Double Outputs:
0 to 125
points
Number of double floating-point output points to configure in the DNP
slave device. Each point will occupy a four-word area in the module
memory.
PLC Double Outputs:
0 to 125
points
Number of double floating-point output points configured above that are
to be sent to the ControlLogix processor.
[Section]/Item
Description
[DNP Slave Binary Inputs]
DNP database binary input override values
# This area is to override the class assignment for binary input database
points. Enter list of points between the START and END labels.
#
# Point# Class
START
END
[Section]/Item
Description
[DNP Slave Analog Inputs]
DNP database analog input override values
START
# This area is to override the class and deadband assignment for analog
input database points. Enter list of points between the START and END
labels.
#
# Point# Class Deadband
START
END