MVI56-DNP
♦
ControlLogix Platform
Configuring the MVI56-DNP Module
DNP 3.0 Server
User Manual
ProSoft Technology, Inc.
Page 37 of 171
July 21, 2011
[Section]/Item Range
Description
CD Time Before Receive:
0 to 65535
Defines the number of milliseconds to wait before receiving characters
after the CD signal is recognized as high.
BI Class:
0 to 3
This parameter specifies the default class to be utilized for all the binary
input points in the DNP database that are not defined in the override list
section.
AI Class:
0 to 3
This parameter specifies the default class to be utilized for all the analog
input points in the DNP database that are not defined in the override list
section.
Float Class:
0 to 3
This parameter specifies the default class to be utilized for all the
floating-point input points in the DNP database that are not defined in
the override list section.
Double Class:
0 to 3
This parameter specifies the default class to be utilized for all the double
floating-point input points in the DNP database that are not defined in
the override list section.
AI Deadband:
0 to 32767
This parameter specifies the default deadband value assigned to all
points not defined in the override list for the analog input point type in
the DNP database.
Float Deadband:
0 to
maximum
float value
This parameter specifies the default deadband value assigned to all
points not defined in the override list for the floating-point input point
type in the DNP database.
Double Deadband:
0 to
maximum
double value
This parameter specifies the default deadband value assigned to all
points not defined in the override list for the double floating-point input
point type in the DNP database.
Select/Operate Arm Time:
1 to 65535
milliseconds
Time period after select command received in which operate command
will be performed. After the select command is received, the operate
command will only be honored if it arrives within this period of time.
Write Time Interval:
0 to 1440
minutes
Time interval to set the need time IIN bit (0=never), which will cause the
Master to write the time. Stored in milliseconds in the module memory.
Data Link Confirm Mode:
Coded Value
(N=Never,
S=Sometime
s, A=Always)
IED can request acknowledgement from Master station when sending
data. The codes are as follows: 0=Never, 1=Sometimes, 2=Always
Data Link Confirm Tout:
(Tout = Timeout)
1 to 65535
milliseconds
Time period to wait for Master Data Link confirmation of last frame sent.
This time is in milliseconds. This parameter is only used if the frame is
sent with confirmation requested.
Data Link Max Retry:
0 to 255
retries
Maximum number of retries at the Data Link level to obtain a
confirmation. If this value is set to 0, retries are disabled at the data link
level of the protocol. This parameter is only used if the frame is sent with
confirmation requested.
App Layer Confirm Tout:
1 to 65535
milliseconds
Event data contained in the last response may be sent again if not
confirmed within the millisecond time period set. If application layer
confirms are used with data link confirms, ensure that the application
layer confirm timeout is set long enough.
Unsolicited Response:
Yes or No
Set if the slave unit will send unsolicited response messages. If set to
No, the slave will not send unsolicited responses. If set to Yes, the slave
will send unsolicited responses.
Class 1 Unsol Resp Min:
1 to 255
events
Minimum number of events in Class 1 required before an unsolicited
response will be generated.
Class 2 Unsol Resp Min:
1 to 255
events
Minimum number of events in Class 2 required before an unsolicited
response will be generated.