Reference MVI56-DNP
♦
ControlLogix Platform
User Manual
DNP 3.0 Server
Page 146 of 171
ProSoft Technology, Inc.
July 21, 2011
OBJECT REQUEST
RESPONSE
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
NOTES
110 0
Not Defined
Not Defined as the variation
determines the string length
1
to
100
Octet String
1
00, 01,
06, 07,
08, 17,
28
129, 130 00, 01,
07, 08,
17, 28
8 *
Var #
The module will return this
variation for the points
defined in the module. The
variation determines the
returned string length.
No Object
13
Slave supports the Cold
Restart Function and will
return Obj 52, Var 2, Qual 7,
Cnt 1
14
Slave supports the Warm
Restart Function and will
return Obj 52, Var 2, Qual 7,
Cnt 1
20
Slave supports the Enable
Unsolicited Function
21
Slave supports the Disable
Unsolicited Function
23
Slave supports the Delay
Measurement & Time
Synchronization Function and
will return Obj 52, Var 2, Qual
7, Cnt 1