4.5.2 System Configuration Errors
Error Code
Name
Description
100
Too many binary input points
Too many binary input points are configured for
the module. Maximum value is 15360.
101
Too many binary output points Too many binary output points are configured for
the module. Maximum value is 15360.
102
Too many counter points
Too many counter points are configured for the
module. Maximum value is 480.
103
Too many analog input points
Too many analog input points are configured for
the module. Maximum value is 960.
104
Too many analog output points Too many analog output points are configured for
the module. Maximum value is 960.
105
Too many binary input events
Too many binary input events are configured for
the module. Maximum value is 400.
106
Too many analog input events
Too many analog input events are configured for
the module. Maximum value is 400.
107
Invalid analog input deadband Deadband value for analog input events is out of
range. Value must be in the range of 0 to 32767.
108
Not enough memory
There is not enough memory in the module to
configure the module as specified.
109
Invalid block transfer delay for
blocks 251 and 252
(error/status blocks)
Block transfer delay value specified is too low.
110
File count invalid
The file count must be in the range of 0 to 6.
111
Invalid file record size
The file record size must be in the range of 1 to
120.
112
Invalid block identification code
for file
The file block transfer code must be in the range
of 100 to 120.