MVI56-DNP
♦
ControlLogix Platform
Reference
DNP 3.0 Server
User Manual
ProSoft Technology, Inc.
Page 127 of 171
July 21, 2011
SOE Binary Input Events Block (9961) with 1972 Time Base (GMT Time)
Block Identification Code 9961 is used by the PLC to send a set of SOE binary
input events to the module using 64-bit time code based at a starting point of
January 1st, 1972. This block is for RS Logix versions prior to version 16.
Block Request from Processor to Module (9961)
Word Offset in
Block
Data Field(s)
Description
0 Block
ID
This field contains the value of 9961 identifying the SOE
event block to the module.
1 Event
Count
This field contains the number of events contained in the
block. Valid values for this field are 1 to 20.
2 Sequence
Counter
This field is used to hold the sequence counter for each
9961 block transfer. This is used to synchronize and
confirm receipt of the block by the module.
3
DNP Binary Input
Data point
This is the data point in the DNP binary input database
represented by the event.
4 to 7
64-bit time
This is the 64-bit time value generated by the SOE module.
8
Value
This is the value for the event data. It is either a 0 or 1.
9 to 14
Six words of data for Event #2.
15 to 20
Six words of data for Event #3.
21 to 26
Six words of data for Event #4.
27 to 32
Six words of data for Event #5.
33 to 38
Six words of data for Event #6.
39 to 44
Six words of data for Event #7.
45 to 50
Six words of data for Event #8.
51 to 56
Six words of data for Event #9.
57 to 62
Six words of data for Event #10.
63 to 68
Six words of data for Event #11.
69 to 74
Six words of data for Event #12.
75 to 80
Six words of data for Event #13.
81 to 86
Six words of data for Event #14.
87 to 92
Six words of data for Event #15.
93 to 98
Six words of data for Event #16.
99 to 104
Six words of data for Event #17.
105 to 110
Six words of data for Event #18.
111 to 116
Six words of data for Event #19.
117 to 122
Six words of data for Event #20.
123 to 247
Spare
Not Used