MVI56-DNP
♦
ControlLogix Platform
Start Here
DNP 3.0 Server
User Manual
ProSoft Technology, Inc.
Page 25 of 171
July 21, 2011
3
Set the Module Properties:
Parameter Value
Name
Enter a module identification string. Example: DNP.
Description
Enter a description for the module. Example: DNP 3.0
Server over Ethernet Communication Module
Comm Format
Select
DATA-INT
(no other option will work)
Slot
Enter the slot number in the rack where the MVI56-DNP
module is located.
Input Assembly Instance
1 (must use this value)
Input Size
250 (must use this value)
Output Assembly Instance
2 (must use this value)
Output Size
248 (must use this value)
Configuration Assembly Instance
4 (must use this value)
Configuration Size
0 (must use this value)
4
Select the Requested Packet Interval value for scanning the I/O on the
module. This value represents the minimum frequency the module will handle
scheduled events. This value should not be set to less than 1 millisecond.
Values between 1 and 10 milliseconds should work with most applications.
On the Connection tab, set the RPI value for your project. Click OK to
confirm.