MVI56-DNP
♦
ControlLogix Platform
Ladder Logic
DNP 3.0 Server
User Manual
ProSoft Technology, Inc.
Page 59 of 171
July 21, 2011
Name Style
Description
Mem_AppTx INT This value represents the number of application layer transmit
memory blocks allocated.
Mem_DevErr INT This value represents the number of memory allocation errors for
device blocks.
Mem_PhyErr INT This value represents the number of memory allocation errors for
physical layer frame blocks.
Mem_DLRErr INT
This value represents the number of memory allocation errors for
data link layer receive blocks.
Mem_DLTErr INT This value represents the number of memory allocation errors for
data link layer transmit blocks.
Mem_AppRErr INT
This value represents the number of memory allocation errors for
application layer receive blocks.
Mem_AppTErr INT
This value represents the number of memory allocation errors for
application layer transmit blocks.
Mstr_Sync INT This value counts the number of times a sync error occurs. The
error occurs when extra bytes are received before the start bytes
(0x05 and 0x64) are received.
Mstr_Length INT This value counts the number of times an invalid length byte is
received. If the length of the message does not match the length
value in the message, this error occurs.
Mstr_CRC INT
This value counts the number of times a bad CRC value is
received in a message.
Scan_Count
DINT
Program scan counter
Mem_Free
DINT
Free memory in module
P1_TX_State
INT
Value of the DNP Slave state machine for transmit.
FloatEvents INT Total number of events generated for analog floating-point input
data points.
DoubleEvents INT
Total number of events generated for analog double, floating-
point input data points.
EventQueue
INT
Number of event messages waiting to send to processor.
EvtQueueOF INT Flag to indicate if the event message queue has overflowed. If
more than 200 event messages are received on the master port
and they are not sent to the processor, this flag will be set (1).
The flag will clear after the messages are sent to the processor.
Local Slave IIN
Bits
INT
Local slave IIN bits being reported to controlling station when the
module is acting as a DNP slave
Ladder logic is required to transfer the data sent from the module to the
processor into this data object. If the ladder logic is present and the module is
operating, this object can be viewed in the Controller Tags Monitor window to
determine current module status.