Programming the Outputs
Page 71 of 102
10.7 Configuring an Event-Other Relay
10.7.1 Schedules, Prebleeding, Lockout and
With a Sensor
Events are typically used to feed biocides on a
pre-determined schedule with weekly or daily
schedules being the most popular. An example
might be; Every Monday feed biocide A for 20
minutes at 7 AM, then feed biocide B every
Thursday, for 25 minutes at 7 AM. You can
choose a 28 day cycle to accommodate feeding
every other week.
Schedules generally do not follow a calendar.
Daily choices repeat every day. If you choose the
28 day cycle, the next screen will tell you which
week you are in, 1
–
4. Weekly entries match a
weekly calendar. Sunday is day 1 and Saturday is
day 7.
Any event has an option to configure prebleeding
and/or lockout to maximize the effect of the
product. The idea of locking the bleed valve during
and after feeding a non-oxidizing biocide improves
effectiveness by increasing contact time.
Programming a prebleed ensures that the tower
not cycle up above the blowdown set-point
avoiding a scaling situation. The prebleed setup
will open the bleed valve until a timer has expired
or a low conductivity set-point is reached. The
feed is delayed by this action.
If you have not enabled the Feed relay, see
section
10.6 Configuring a Feed Relay
Use an event in conjunction with a sensor to limit ON
time during the event. See
9.5.5 Feed Based on a
Sensor with Event Control
10.7.1.1 Prebleed/Lockout
The following steps are a continuation of
10.7.1
Schedules, Prebleeding, Lockout and With a
Sensor
If your event does not require a Prebleed or Lockout,
skip to section
10.7.2.1 Adding Events
NOTE: In addition to a feed relay, this procedure
requires the use of a blowdown relay. See section
10.5 Configuring a Blowdown Relay
1- From the Daily, Weekly or 28 Day screen,
choose
F3
CONFIG
as before.
2- Press
F1
, Select to choose
Prebleed
3- Scroll down to find the blowdown relay and
press
F1
to
SELECT
it
4- Scroll down to find the Conductivity sensor and
press
F1
to
SELECT
it.
5- Press
F3
to return to the Configuration menu
and
F1
to Select
Prebleed
again.
6- Use the arrows to adjust the Prebleed time.
Press
F1
to
SAVE
7- Press
F3
,
Config
.
8- Press
F1
to choose
Lockout
9- Use the arrows to edit the lockout time. This
value should include the feed time of the pump.
It is not the length of time after the pump stops.
10- Press
F1
to
Save
.
We are now ready to add events to the relay. The
relay should be named as well to avoid confusion.
This menu is the same for Pulse relay event
configuration.