Mounting and Installation
Page 44 of 102
Pin 1 on the Prominent amperometric
sensor is connected to the V+ terminal
Pin 2 on the sensor is connected to the ‘IN’
terminal
Shown connected to XE1
Figure 55 Amperometric probe to 4-20mA Input Driver
Figure 56 Three wire 4-20mA inputs that utilize V+
MilliAmp inputs from powered devices do not need on-board V+. The + wire from the Input device, (analyzer, PLC, etc),
connects to the ‘IN’ terminal and the –
wire to the ‘GND’.
Figure 57 Two wire remotely powered
Analog input
Analyzers and computer systems, DCS, PLC etc, typically have 120VAC.
Therefore signals from these devices can be powered from them. However, the
signals often have the option to allow the current loop to be powered from the
receiving end. In this case, the receiving end is this controller.
The purpose of this page is to show how to wire inputs from devices that need to
be powered from the controller, figures 55 and 56, and inputs that are powered
remotely, figure 57.