Programming the Outputs
Page 62 of 102
9.11.1 Changing or Unlinking an Analog Input
Tied to an Output Relay
Inputs linked to outputs must be un-linked prior to
being disabled.
Analog inputs tied to Feed type relays, use
pictogram
A,
Blowdown type use
B
, and Event
–
other use
C
.
1- Press
MENU
2- Scroll down to Set Feed Mode if used to
control a pump or Set Blowdown Mode if the
relay is used for bleed. Press
OK
3- (Examples of each type)
4-
Scroll down to the relay indicated in the ‘In
Use’ menu
(Step 6 in 9.11) and press
OK.
5- Change the relay to a different type of
control program, press
OK
and skip to step
6, or press
OK
for Sensor Control
6-
Scroll up or down to the new sensor and
press
OK
7- Press
F1
, ‘Select’ to save this choice.
8- Press
ESC
, Escape
Return to the 9.11
Disable an Analog or Digital Input
menu, to finish.