Programming the Inputs
Page 59 of 102
9.10 Configuring Digital Inputs
9.10.1 Configure a Digital Input as a Water
Meter:
NOTE: All digital inputs O-V can be configured for a
pulsing water meter
1- To Enable and Set digital input press
MENU
2- Scroll
to
System
and press
OK
3- Scroll to Enable I/O and press
OK
4- Scroll to select the desired input (O through
V) and press
F3
5- Press
F3
again to switch from METER to
CONTACT if necessary, then press
OK
6- Press
MENU
7- Scroll to Water Meter Setup then press
OK
8- Scroll down to your meter, then press
OK
9- Use
F3
to switch to Vol/Contact if
necessary, then use Up/Down and
Left/Right arrow keys to set gallon per
contact or to adjust the K factor, then press
F1
to SAVE.
Note:
See
9.2 Naming an Input or Output
to
rename the relay for example to
“Makeup Flow”