Programming the Inputs
Page 58 of 102
x
Diagnostic 2: sensor Raw value
x
Diagnostic 3:Gain, changes based on
calibration
x
Diagnostic
4:Offset,
x
Diagnostic 5: reports any Alarm
x
Diagnostic 12:if sensor connected it will
display (Sensor OK Connected) if no sensor
connected to terminals (Sensor disabled
Disconnected)
x
Diagnostic 13:will display phantom input
Temperature value and also if the Thermal
flow switch is ON/OFF.
In this example Flow value should be higher
than 960 to display Flow ON.
Note: Sensor Value = Raw x GAIN + OFFSET
For example=235x8.5+0=1998uS about 2000uS