Basic Series Network Thermostat Configuration Guide, Release 3.0
Part No. 600-01000-201, Rev. 1
CHAPTER 3: Configuring the Thermostat Using the TMI
Use
Table 3-2
to set the
General Settings
parameters such as the thermostat name and
location and enable or disable alarm settings and filter replacement reminders.
Table 3-2 General Settings Field Descriptions
Field
Description
Zone Name
Device Name
Enter a unique 13 character identifier for the thermostat. You can
use the thermostat location in this field (i.e. Main Lobby). This
identifier is known as the host name within the data network.
Site Name
Enter a 25 alpha-numeric character name used to identify the
thermostat if more than one thermostat intercommunicates with
the Proliphix Web Server. (See the
Proliphix Remote Access
Guide.
)
Thermostat
Serial Number
Displays an eight digit alpha-numeric thermostat serial number
(e.g. 8438F399).
SW Ver / HW Rev
Displays the software version / hardware revision .
Temperature Scale
Select either the Fahrenheit or Celsius temperature scales.
Fahrenheit
(default) – All thermostat temperature readings
and reporting are displayed in the Fahrenheit temperature
scale (
°
F).
Celsius
– All thermostat temperature readings and reporting
are displayed in the Celsius temperature scale (
°
C).
Display Contrast
Select a value between
20
(lowest contrast between the graphics
characters and the background) and
40
(highest character
contrast to the background) to indicate the LCD display contrast
control.
20, 22, 24, 26, 28 (default), 30, 32, 34, 36, 38, 40
Alarms
Low Temp(erature) Limit
Select a value
or
Disable
to indicate the low temperature
threshold detection status. The value set by this parameter is
monitored by the thermostat and compared against the current
Zone Temperature
. If the current
Zone Temperature
falls below
this value, an alarm condition is set and the status is displayed on
the
Status & Control Page (page 3-9)
. In addition, this alarm will
be sent to the Proliphix web site to trigger an email notification if
this function is
Enabled
.
This is a major (red) alarm condition. (See
Figure 3-4 on
page 3-13
.)
Disable
(default) – No low temperature limit is set.
-30
°
F(-34.5
°
C) to 200
°
F(93
°
C)