Beta Draft Confidential
General Settings Page
Basic Series Network Thermostat Configuration Guide, Release 3.0
3-15
Part No. 600-01000-201, Rev. 1
Low Temp(erature) Dismiss
If a
Low Temp Limit
alarm is pending, you must clear this
condition. In
Figure 3-4 on page 3-13
, a
Low Temp Limit
alarm
is set and is noted in the
Low Temp Dismiss
field. Note that the
Condition Repaired
box must be checked and the
Zone
Temperature
must be above the
Low Temp Limit
or the
Low
Temp Limit
must be set to
Disable
for the alarm condition to be
cleared upon a
Submit
.
Disable (default)
– No low temperature limit is set.
-30
o
F(-34.5
o
C) to 200
o
F(93
o
C)
High Temp(erature) Limit
Select a value or
Disable
to indicate the high temperature
threshold detection status. The value set by this parameter is
monitored by the thermostat and compared against the current
Zone Temperature
. If the current
Zone Temperature
rises above
this value, an alarm condition is set and the status is displayed on
the
Status & Control Page (page 3-9)
. In addition, this alarm is
sent to the Proliphix web site to trigger an email notification if
this function is
Enabled
.
Disable
(default) – No high temperature limit is set.
-30
°
F(-34.5
°
C) to 200
°
F(93
°
C)
This is a major (red) alarm condition. (See
Figure 3-4 on
page 3-13
.)
High Temp(erature) Dismiss
If a
High Temp Limit
alarm is pending, you must clear this
condition. In
Figure 3-4 on page 3-13
, a
High Temp Limit
alarm is set and is noted in the
High Temp Dismiss
field. Note
that the
Condition Repaired
box must be checked and the
Zone
Temperature
must be below the
High Temp Limit
or the
High
Temp Limit
must be set to
Disable
for the alarm condition to be
cleared upon a
Submit
.
Disable (default)
– No low temperature limit is set.
-30
o
F(-34.5
o
C) to 200
o
F(93
o
C)
Filter (change) Reminder
Select an interval between
Disable
(default) and
365
days to
remind you that the HVAC system requires maintenance. This
feature allows you to set time intervals between changing and/or
cleaning the HVAC filter. If enabled, an alarm condition is set
after the pre-set interval has expired, and is displayed on the
Status & Control Page (page 3-9)
. In addition, this alarm is sent
to the Proliphix web site to trigger an email notification if this
function is
Enabled
.
This is a minor (yellow) alarm condition.
Disable
(default) – Interval reminder disabled.
10, 30, 60, 90, 120, 240, 365 Runtime Days
– The runtime
interval after which an alarm will be set to remind the user of
the need for HVAC maintenance.
Table 3-2 General Settings Field Descriptions (Continued)
Field
Description