68
Load Break Switch Control
ERT-200S
Range
FWD ~ REV
Default
FWD
Step
Set the CT Direction
I/O Config/ 7. InterLock Set
Range
Yes / No
Default
Step
-
Close Interlock
The following close interlock condition blocks the switch
to be closed manually or automatically if it’s selected as
“Yes”.
-
Open Interlock
Opened under rated load (700A)
I/O Config/ 8. FI Reset Set
Range
Manu / Auto
Default
Auto
Step
Auto Mode : FI reset automatically when voltage is input
after FI Set
Manu Mode : FI Reset button or communication FI Reset
command only FI reset
FI Clear Time : Clear the FI status at the set time after
determining the fault type.
FI Clear Time = 0 (FI CLEAR Function Disable)
I/O Config/ 9. Pulse Set
Range
1,000 ~ 5,000ms
Default
1,200ms
Step
1ms
Set Motor Output Pulse Time.
Close or Open pulse width shall be set longer than switch
operating time.