66
Load Break Switch Control
ERT-200S
7.2.
System Config Menu
Locate the cursor on
“SystemConfig” in the main menu, and move to this menu by pressing
[ENTER]
.
SystemConfig menu has the following submenu.
7.2.1.
I/O Config
Locate the cursor on
“1. I/O config” in System Config menu and move to this menu by pressing
[ENTER]
button.
In this menu, various elements related to the system can be set. It has the following submenu.
Range
Step
Def.
Unit
Min
Max
System Frequency
50
60
10
50
Hz
System Type
3P4L
3P3L
3P4L
Rated Voltage
3800
26000
100
13200
V
CT Ratio
100
2000
10
1000
A
NCT Ratio
100
2000
10
1000
A
CT Direction
FWD
REV
FWD
Interlock Live Load
No
Yes
No
Interlock Sync
’ Fail
No
Yes
No
Open Inter Lock
No
Yes
Yes
FI Reset Select
Manu
Auto
Manu
FI Clear Time
0
600
1
0
sec
Pulse Set (OPEN)
1200
5000
1
1200
ms
Pulse Set (CLOSE)
1200
5000
1
1200
ms
Batt
’ Test Time Set
0
100
1
24
h
Ref Phase
A /B /C
A
Phase Rotation
ABC / ACB
ABC
Содержание ERT-200S
Страница 1: ...Feeder Remote terminal Unit ERT 200S Manual www powersys kr...
Страница 13: ...13 Load Break Switch Control ERT 200S 2 5 Function BlockDiagram...
Страница 38: ...38 Load Break Switch Control ERT 200S 5 3 3 Menu structure tree Figure Menu Tree Structure...
Страница 42: ...42 Load Break Switch Control ERT 200S...
Страница 96: ...Appendix 1 Drawings 1 Enclosure Control Cabinet...
Страница 97: ...97 Load Break Switch Control ERT 200S...