21
Load Break Switch Control
ERT-200S
2.10.
Event Record
2.10.1.
Event Record
The event recorder feature allows the time tagging of any change of state (Event) in the relay. As an event
occurs, the actual event condition is logged as a record along with a time and date stamp to a resolution of 1
millisecond. There is capacity for a maximum of
1375
event records that can be stored in the relay and when
the event buffer is full any new record will over-write the oldest.
All events can be uploaded over the data communications channel(s) and can be displayed in the
‘R
-Manager
’
SW package in chronological order, allowing the sequence of events to be viewed.
Events are also made available spontaneously to an Modbus RTU or DPN 3.0 compliant control system.
Event List
Description
Max
I/O Event
Status Change of binary Input/Output
➔
SW State
➔
Main Lock
➔
GAS Low
➔
Door State
125
F/I Event
Operated status of Fault Indication
➔
Fault count : a,b,c,n, all
➔
Latest fault current, phase and time
250
System Event
Status Change of System
➔
System Reset
➔
Set Change
➔
Communication Error
➔
AC Loss
125
Control Event
Controlled status of ERT-200S
➔
SW Control
➔
Control
➔
Locked
➔
FI Reset
➔
Battery test
125
Measure Event
Measure status of ERT-200S
1)
Average 15
➔
Pa/Pb/Pc/TT
➔
Qa/Qb/Qc/TT
➔
Ia/Ib/Ic/TT
2)
Daily Max
125 * 6
Total : 750
Содержание ERT-200S
Страница 1: ...Feeder Remote terminal Unit ERT 200S Manual www powersys kr...
Страница 13: ...13 Load Break Switch Control ERT 200S 2 5 Function BlockDiagram...
Страница 38: ...38 Load Break Switch Control ERT 200S 5 3 3 Menu structure tree Figure Menu Tree Structure...
Страница 42: ...42 Load Break Switch Control ERT 200S...
Страница 96: ...Appendix 1 Drawings 1 Enclosure Control Cabinet...
Страница 97: ...97 Load Break Switch Control ERT 200S...