52
Load Break Switch Control
ERT-200S
Range
0.1 ~ 180.0 sec
Default
0.2
Step
0.1 sec
Set Cold load Time
Phase Fault / Inrush Restraint
Range
Yes / No
Default
No
Step
Set
[YES / No]
of direction Detection, when occurs Inrush
Restraint.
Phase Fault / Direction Function use
Range
No Use / Use
Default
Use
Step
Set
[YES / No]
of direction Detection, when occurs Inrush
Restraint.
Phase Fault / Direction Reference Voltage
Range
5% ~ 85%
Default
10%
Step
1%
Phase Fault / Direction MTA
Range
0 ~ 359 deg
Default
0
Step
1 deg