59
Load Break Switch Control
ERT-200S
7.1.7.
Sectionalize Setting
The LBS can be configured as a sectionalizer that trips during the dead time of an upstream Recloser after a
configurable number of supply interrupts.
Range
Step
Def.
Unit
Min
Max
Mode
VIT
VT
VIT
Fault Count
1
3
1
2
Reset Time
20
240
1
Sec
Function Use
No
Yes
No
Sectionalize / Mode Select
Range
VIT ~ VT
Default
VIT
Step
Select mode to detect operation as voltage or current or
voltage only
Sectionalize / Fault count Set
Range
1 ~ 3
Default
2
Step
1
The number of supply interrupts counted exceeds the trip
after setting at counter
Caution:
Pay attention to the sectionbalizer setting
according to the Operation Open Time and Recloser
setting of Mechanism
Sectionalize / Reset Time Set
Range
20 ~ 240 sec
Default
30 sec
Step
1 sec
When sectionalizingis enabled, the upstream Recloser
reclose time must exceed 20 ~ 240 seconds to allow for
the opening time of the LBS.