
67
Load Break Switch Control
ERT-200S
I/O Config/ 1. System Frequency Set
Range
50, 60 Hz
Default
60 Hz
Step
Frequency setting. This value is used to set digital
sampling ratio.
I/O Config/ 2. System Type
Range
380 ~ 26,000V
Default
26,000 V
Step
10V
In Line system, rated voltage of power supply system is
set.
I/O Config/ 3. Rated Voltage Set
Range
380 ~ 26,000V
Default
26,000 V
Step
10V
In Line system, rated voltage of power supply system is
set.
I/O Config/ 4. CT Ratio Set
Range
100 ~ 2,000 A
Default
1,000 A
Step
10 A
Set the CT rate.
I/O Config/ 5. NC.T Ratio Set
Range
100 ~ 2,000 A
Default
1,000A
Step
10 A
Set the NCT rate
I/O Config/ 6. C.T Direction Set
Содержание ERT-200S
Страница 1: ...Feeder Remote terminal Unit ERT 200S Manual www powersys kr...
Страница 13: ...13 Load Break Switch Control ERT 200S 2 5 Function BlockDiagram...
Страница 38: ...38 Load Break Switch Control ERT 200S 5 3 3 Menu structure tree Figure Menu Tree Structure...
Страница 42: ...42 Load Break Switch Control ERT 200S...
Страница 96: ...Appendix 1 Drawings 1 Enclosure Control Cabinet...
Страница 97: ...97 Load Break Switch Control ERT 200S...