Load Break Switch Control
ERT-200S
Inrush Detect Set
Range
0.1 ~ 180.0 sec
Default
0.2
Default
0.1 sec
Inrush Detect
Inrush Multiply Set
Range
100 ~ 1000 %
Default
500%
Step
10%
Function use
Range
Default
Step
Set
[Use / No Use]
of direction Detection, when occurs
Inrush detect.
7.1.4.
FI Reset Time Setting
Range
Step
Def.
Unit
Min
Max
FI Reset Time
1
180
1
20
S
Function use
Range
1 ~ 180 s
Default
20s
Step
1 s
1)
Set
[Use / No Use]
of direction Detection, when
occurs Inrush detect.