14
Load Break Switch Control
ERT-200S
2.6.
Fault Detect and Sectionalizing Functions
Phase Fault Detection
Phase Fault Threshold Current Setting Range
(Pick up Current)
5 to 900A
Default : 400A / step : 1A
Definite Time for Fault to Persist Setting Range
(Detection Time)
0.01 to 10.0 sec
Default : 0.05s / step : 0.01s
Inrush Restraint
Yes/NoDefault : No
Cold Load Pickup
100 ~ 500%
Default : 200% / step : 10%
Cold Load Time
0.1to 180sec
Default : 0.2sec / step : 0.1sec
Direction Detection Enable
No Use/Use Default : Use
Direction Voltage Pickup
5 ~ 85 %
Default : 10% / Step : 1 %
Direction MTA
0 ~ 359 deg
Default : 0 deg / step : 1 deg
Ground Fault Detection
Earth Fault Threshold Current Setting Range
(Pick up Current)
5 to 900 A
Default : 60A / step : 1A
Definite Time for Fault to Persist Setting Range
(Detection Time)
0.01 to 10.0 sec
Default : 0.05s / step : 0.01s
Inrush Restraint
Yes/No
Default : No
Direction Detection Enable
No Use/Use Default : Use
Direction Voltage Pickup
5 ~ 85 %
Default : 10% / Step : 1 %
Direction MTA
0 ~ 359 deg
Default : 0 deg / step : 1 deg
Inrush Detection
2
nd
Harmonic Setting Range
5 ~ 50 %
Default : 20 % / step : 1%
Detection Time
0.02 ~ 1sec
Default : 0.02 / step : 0.01 sec
Inrush Time
0.1~180.0 sec
Default : 0.2 s step : 0.1 sec
Multiple
100 ~ 1000 %
Default : 200% / step : 10%
FI Reset Time
Содержание ERT-200S
Страница 1: ...Feeder Remote terminal Unit ERT 200S Manual www powersys kr...
Страница 13: ...13 Load Break Switch Control ERT 200S 2 5 Function BlockDiagram...
Страница 38: ...38 Load Break Switch Control ERT 200S 5 3 3 Menu structure tree Figure Menu Tree Structure...
Страница 42: ...42 Load Break Switch Control ERT 200S...
Страница 96: ...Appendix 1 Drawings 1 Enclosure Control Cabinet...
Страница 97: ...97 Load Break Switch Control ERT 200S...