Function
Prog.
no.
Level
1)
Standard value
End
643
Eu
--.-- (day. month)
Operating level
Frost protection | Reduced
648
Eu
Frost Protection
Holidays heating circuit 2
Parameter only visible, if heating circuit 2 exists!
Preselection
Period 1 ... 8
651
Eu
Period 1
Start
652
Eu
--.-- (day. month)
End
653
Eu
--.-- (day. month)
Operating level
Frost protection | Reduced
658
Eu
Frost Protection
Holidays heating circuit 3
Parameter only visible, if heating circuit 3 exists!
Preselection
Period 1 ... 8
661
Eu
Period 1
Start
662
Eu
--.-- (day. month)
End
663
Eu
--.-- (day. month)
Operating level
Frost protection | Reduced
668
Eu
Frost Protection
Heating circuit 1
Operating mode Heating circuit 1
Protection | Automatic | Reduced | Comfort
700
Eu
Automatic
Comfort setpoint
710
Eu
20.0°C
Reduced setpoint
712
Eu
16.0°C
Frost protection setpoint
714
Eu
10.0°C
Heating curve slope
720
Eu
1.50
Heating curve displacement
721
E
0.0°C
Heating curve adaption
Off | On
726
E
Off
Summer/winter heating limit
730
Eu
18°C
24-hour heating limit
732
E
- 3°C
Flow temp setpoint min
740
E
8°C
Flow temp setpoint max
741
E
80°C
Flow temp setpoint room stat
742
E
65°C
Room influence
750
C
- - - %
Room temp limitation
760
E
1°C
Boost heating
770
E
5°C
Quick setback
Off | Down to reduced setpoint | Down to frost prot setpoint
780
E
Down to reduced set-
point
Optimum start control max
790
E
0 min
Optimum stop control max
791
E
0 min
Reduced setp increase start
800
E
- - -°C
Reduced setp increase end
801
E
15°C
Programming
358 488 09.10
Gas-fired fuel value boiler EuroCondense three 125-300 kW
11
Содержание Eurocondense three
Страница 101: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 101 ...
Страница 103: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 103 ...
Страница 105: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 105 ...
Страница 107: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 107 ...
Страница 109: ...Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 109 ...
Страница 111: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 111 ...
Страница 115: ...3 2 Legend Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 115 ...
Страница 117: ...Space for notes 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 117 ...
Страница 118: ...Space for notes 118 Gas fired fuel value boiler EuroCondense three 125 300 kW 358 488 09 10 ...
Страница 119: ...Space for notes 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 119 ...