Tab. 5: Check no. heating circuit (prog.-no. 6217)
Heating circuit 3
Heating circuit 2
Heating circuit 1
0 No heating circuit
00 No heating circuit
00 No heating circuit
1 Circulation via boiler pump
01 Circulation via boiler pump
01 Circulation via boiler pump
2 Heating circuit pump
02 Heating circuit pump
02 Heating circuit pump
3 Heating circuit pump, mixing
valve
03 Heating circuit pump, mixing
valve
03 Heating circuit pump, mixing
valve
Software version
(6220)
Display of the actual software version.
LPB-system
Device address/Segment add-
ress
(6600/6601)
The two-part LPB address of the controller consists of the 2-digit segment num-
ber and the 2-digit device number.
Bus power supply function
(6604)
-
Off
: the power supply of the bus system does not take place through the con-
troller.
-
Automatically
: the power supply of the bus system is switched on and off by
the controller depending on the power requirement of the bus system..
Bus power supply state
(6605)
-
Off
: the power supply of the bus system through the controller is currently inac-
tive.
-
On
: the power supply of the bus system through the controller is currently acti-
ve.
Display systemmessages
(6610)
This setting allows system messages which are transmitted via LPB to be suppres-
sed on connected operating elements.
Alarm delay
(6612)
Settling out of the alarm on the BM module can be delayed in the base device by
an adjustable time. This allows the prevention of unnecessary messages to a ser-
vice location from briefly occurring malfunctions (e.g. temperature monitor quer-
ied, communication errors). However, it must be realised that briefly occurring
malfunctions which continue and quickly occur again, are also filtered out with
this.
Display systemmessages
(6610)
If the setting Central is activated under progr. no. 6221 and 6223, the action for
this setting can be set. The following settings are possible:
-
Segment
: the changeover is done for all controllers in the same segment.
-
System
: the changeover is done for all controllers in the entire system (that is in
all segments). The controller must be located in segment 0!
Summer changeover
(6621)
-
Locally
: the local heating circuit is switched on and off depending on prog. no.
730, 1030 or 1330.
-
Centrally
: depending on the settings made in prog no. 6620 either the heating
circuit in the segment or in the entire system is switched on and off.
Optg mode changeover
(6623)
-
Locally
: the local heating circuit is switched on and off.
-
Centrally
: depending on the settings made in prog no. 6620 either the heating
circuit in the segment or in the entire system is switched on and off.
Programming
358 488 09.10
Gas-fired fuel value boiler EuroCondense three 125-300 kW
71
Содержание Eurocondense three
Страница 101: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 101 ...
Страница 103: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 103 ...
Страница 105: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 105 ...
Страница 107: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 107 ...
Страница 109: ...Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 109 ...
Страница 111: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 111 ...
Страница 115: ...3 2 Legend Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 115 ...
Страница 117: ...Space for notes 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 117 ...
Страница 118: ...Space for notes 118 Gas fired fuel value boiler EuroCondense three 125 300 kW 358 488 09 10 ...
Страница 119: ...Space for notes 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 119 ...