Reduced setpoint increase
start
(800, 1100, 1400)
Red setpoint increase end
(801, 1101, 1401)
For a relatively small required heating output, the reduced room setpoint can be
raised for cold outside temperatures. The increase is dependent upon the outside
temperature. The lower the outside temperature is, the higher the reduced set-
point for the room temperature is raised. The start of of the increase and the end
point can be set. Between these two points there is a linear increase of the "redu-
ced setpoint" up to the "comfort setpoint".
Fig. 7: Reduced setpoint increase
TOc
TRwA1
TRwA1
TRK
TRR
TAgem
Red setpoint increase start
Red setpoint increase end
Comfort nominal value
Room temperature reduced setpoint
Outside temperature mixed
Continuous pump operation
(809, 1109, 1409)
Using the
continuous pump operation function
switching off the pump can be
suppressed by the quick setback and when reaching the room set point (room
thermostat, room sensor or room model)
-
No
: the heating circuit pump /boiler pump can be switched off by quick setback
or reaching the room set point
-
Yes
: the heating circuit pump/boiler pump remains switched on even during
the quick setback and after reaching the room set point
Overtemp prot pump circuit
(820, 1120, 1420)
This function prevents overheating of the pumped heating circuit by switching-
on and switching-off the pump, if the flow temperature is higher than the flow
temperature required according to the heating curve (e.g. in case of higher de-
mands of other consumers).
Mixing valve boost
(830,1130, 1430)
The heat demand of the mixer heating circuit to the generator is superelevated
above the set value here. This boost should be achieved so that the temperature
fluctuations can be corrected with the mixer valve.
Actuator running time
(834, 941, 1134)
Einstellung der Antriebslaufzeit des verwendeten Mischerventils.
Bei Mischerkreisen wird im Anschluss an den Pumpenkick ein Kick des Mischeran-
triebes durchgeführt (Pumpe ist AUS). In this case, the mixer will be controlled in
direction OPEN and CLOSED.
The time of activation in direction OPEN corresponds to the drive running time.
Programming
358 488 09.10
Gas-fired fuel value boiler EuroCondense three 125-300 kW
41
Содержание Eurocondense three
Страница 101: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 101 ...
Страница 103: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 103 ...
Страница 105: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 105 ...
Страница 107: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 107 ...
Страница 109: ...Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 109 ...
Страница 111: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 111 ...
Страница 115: ...3 2 Legend Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 115 ...
Страница 117: ...Space for notes 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 117 ...
Страница 118: ...Space for notes 118 Gas fired fuel value boiler EuroCondense three 125 300 kW 358 488 09 10 ...
Страница 119: ...Space for notes 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 119 ...