Burner control
Prepurge time
(9500)
Pre-venting time.
Note
: This parameter must only be changed by a heating specialist!
Nominal output prepurging
(9504)
Nominal output fan speed during preventing.
Nominal output ignition load
(9512)
Nominal output fan speed during ignition.
Nominal output Partial load
(9524)
Nominal output fan speed under boiler in LF.
Nominal output Full load
(9529)
Nominal output fan speed under boiler in HF
Prepurge time
(9500)
After-venting time.
Note
: This parameter must only be changed by a heating specialist!
Conversion fan output/speed
increase
(9626)
Conversion fan output/speed
Y-section
(9627)
With this parameter the rotational speed of the fan can be adjusted (e.g. for com-
plex exhaust systems or the conversion of gas condensing boilers for operating
with liquid gas.
- Prog. no. 9626 equates to the incline of the fan characteristic curve
- Prog. no. 9627 equates to the shift of the fan characteristic curve in Y-direction
Info Option
Display of different information values which depend on the current operation
state. Furthermore, informations about the different states are displayed (see sec-
tion
State
).
Programming
358 488 09.10
Gas-fired fuel value boiler EuroCondense three 125-300 kW
81
Содержание Eurocondense three
Страница 101: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 101 ...
Страница 103: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 103 ...
Страница 105: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 105 ...
Страница 107: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 107 ...
Страница 109: ...Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 109 ...
Страница 111: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 111 ...
Страница 115: ...3 2 Legend Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 115 ...
Страница 117: ...Space for notes 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 117 ...
Страница 118: ...Space for notes 118 Gas fired fuel value boiler EuroCondense three 125 300 kW 358 488 09 10 ...
Страница 119: ...Space for notes 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 119 ...