Setpoint source heating
(2056)
When using the generator heating, the swimming pool is heated to the setpoint
set here.
Charging priority solar
(2065)
Setting, of whether the swimming pool heating by solar charging has priority or
not.
Swimming pool temp max
(2070)
This parameter sets whether the swimming pool heating by solar charging has
priority or not. If the swimming pool temp reaches the heating limit set here, the
collector pump is switched off. It is again released if the swimming pool temp has
dropped by 1 °C below the maximum heating limit temperature.
With solar integration
(2080)
Setting, of whether the swimming pool heating can be done by solar energy or
not.
Primary contr/system pump
Flow temp setpoint min
(2110)
Flow temp setpoint max
(2111)
With these boundaries a range for the flow setpoint during heating can be defi-
ned.
Fig. 11: Flow temp setpoint limitations
max
current
min
TV
TFc
TFmax
TFmin
0
10
20
30
40
50
60
70
80
90
100
C0004840
TVmax
TVmin
TVw
TVmax Flow temp setpoint max
TVmin Flow temp setpoint min
TVw Current Flow temp setpoint
Syst pump on heat gen lock
(2121)
This parameter can set whether during active heat generation lock the system
pump will also be locked or not.
-
Off
: The system pump will not be locked.
-
On
: During active heat generation lock the system pump will also be locked.
Mixing valve boost
(2130)
For the admixture the boiler flow temperature actual value must be higher as the
requested setpoint of the mixer flow temperature, since these cannot otherwise
be corrected. The controller from the boiler temperature setpoint from the boost
set here and the current flow temperature setpoint.
Actuator running time
(2134)
Setting the actuator running time of the used mixing valve.
Prim contr/system pump
(2150)
-
Before buffer storage tank
: the primary controller/feed pump is arranged with
existing buffer storage tank hydraulically before the buffer storage tank
-
After buffer storage tank
: the primary controller/feed pump is arranged with
existing buffer storage tank hydraulically after the buffer storage tank
Programming
358 488 09.10
Gas-fired fuel value boiler EuroCondense three 125-300 kW
47
Содержание Eurocondense three
Страница 101: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 101 ...
Страница 103: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 103 ...
Страница 105: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 105 ...
Страница 107: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 107 ...
Страница 109: ...Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 109 ...
Страница 111: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 111 ...
Страница 115: ...3 2 Legend Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 115 ...
Страница 117: ...Space for notes 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 117 ...
Страница 118: ...Space for notes 118 Gas fired fuel value boiler EuroCondense three 125 300 kW 358 488 09 10 ...
Страница 119: ...Space for notes 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 119 ...