Operating level changeover
(898, 1198, 1498)
Using an external timer above the entrances
Hx
it can be selected in which opera-
ting level the heating circuit is switched into.
-
Frost Protection
:
-
Reduced
:
-
Comfort
:
Optg mode changeover
(900, 1200, 1500)
Bei externer Umschaltung der Betriebsart per Hx kann ausgewählt werden, ob bei
Automatikbetrieb vom Komfortsollwert auf den Frostschutzsollwert oder Redu-
ziertsollwert umgeschaltet wird.
DHW
Nominal value
(1610)
Setting the drinking water nominal value
Reduced nominal value
(1612)
The DHW reduced setpoint is set under programme number 1612.
Release
(1620)
-
24h/day
: The DHW temperature will be continuously controlled to the nominal
drinking water temperature value independent from the time switching pro-
grammes.
-
Time programs HCs
: The DHW temperature will be switched over between the
nominal DHW temperature value and the reduced nominal DHW temperature
value depending on the time switching programs. Every time, the switching-on
time will be moved forward.
- In case of several releases per day, it is moved forward by 1 hour (see
Fig. 9
).
Fig. 9: Release depending on the time switching programmes of the hea-
ting circuits (example#)
-
Time program 4
The DHW temperature will be switched over between the nomi-
nal setpoint and the reduced setpoint independent from the time switching pro-
grams of the heating circuits. In this case, the time switching programme 4 will
be used (see
Fig. 10
).
Programming
44
Gas-fired fuel value boiler EuroCondense three 125-300 kW
358 488 09.10
Содержание Eurocondense three
Страница 101: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 101 ...
Страница 103: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 103 ...
Страница 105: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 105 ...
Страница 107: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 107 ...
Страница 109: ...Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 109 ...
Страница 111: ...Wiring plan Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 111 ...
Страница 115: ...3 2 Legend Hydraulic and connection plans 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 115 ...
Страница 117: ...Space for notes 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 117 ...
Страница 118: ...Space for notes 118 Gas fired fuel value boiler EuroCondense three 125 300 kW 358 488 09 10 ...
Страница 119: ...Space for notes 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 119 ...