32
ID-E270-011GB
13
―
1 ÷ 250
T
op
EKS 1 ÷ 2 inputs non-maskable fault until
acknowledgement
14
―
1 ÷ 250
T
op
EKS 1 ÷ 2 inputs technical alarm until
acknowledgement
15
―
―
T
op
Potential outputs fault
16
―
―
T
op
System fault
17
―
―
T
op
Power supply fault
18
―
―
T
op
Potential outputs fault until acknowledgement
19
―
―
T
op
System fault until acknowledgement
20
―
―
T
op
Power supply fault until acknowledgement
21
―
1 ÷ 100
T
op
EWK inputs 1 ÷ 8 fault
22
―
1 ÷ 100
T
op
EWK inputs 1 ÷ 8 technical alarm
Note:
Variants 1, 2, 4, 5 and 15, 16 must not be assigned to LS potential lines as it may result (if this line is
broken or shorted) in improper operation of these outputs.
5.5.7 Information output (TYPE 5)
The information output may be programmed to transmit information about the mode of the system
(control panel and line elements) not being the fire alarm or fault mode.
Table 5.8
Variant
Control
Panel
No.
Time
Parameters
Activation Criterion
1
―
―
Disablement mode
2
―
―
1 ÷ 1024 zones disablement mode
3
―
―
Test mode
4
―
―
1 ÷ 1024 zones test mode
5
―
―
Personnel absent
5.5.8 Reset output (TYPE 6)
The reset output supports only relays and its objective is to generate a reset impulse (duration
approx. 1.5 second), after a fire alarm reset. This type may be used, e.g. to power supply or reset of
detectors requiring a separate power supply source, e.g. flame detectors manufactured by
Det-Tronics.
5.5.9 LK monitoring input
Each of the POLON 4900 control panel 8 monitoring inputs for may be programmed in the following
variants:
-
to monitor the actuation of external devices after receiving an actuation criterion from a
declared relay output or potential output (for TYPE-1, TYPE-2, TYPE-3 outputs);
-
to monitor the proper operation of external devices;