ID-E270-011GB
-
fire alarms;
-
technical alarms and their resets;
-
2
nd
stage alarms;
-
reset;
-
acknowledgement;
-
faults and their resets;
-
non-maskable faults and their resets;
-
tests and their resets;
-
disablements and its resets;
-
output actuation and its resets.
Moreover, the permission for remote operation in the control panel (SYSTEM SETUP -> REMOTE
OPERATION -> OPERATION FROM MONITORING STATION: RE-ENABLED) enables the monitoring
station to remotely acknowledge an alarm or fault and remotely reset an alarm.
A full description of the PMC-4000 protocol is provided in a separate document.
Notes regarding the PMC-4000 monitoring in the network system:
Information from a given control panel may be transmitted to a monitoring station through one of
the RS-232 serial ports or, in the network system, through the network and, next, through the
remote control panel serial port. Both these methods may also be applied simultaneously, i.e.
supervision transmission through own RS-232 port and simultaneous transmission through the
network and, then, through the remote control panel RS-232 port. Thus each control panel may be
supervised in two points at the same time.
In order to ensure correct monitoring transmission over the network, the following data must be
declared in the NETWORK MONITORING option (see the programming manual [PM]):
-
in the control panel to be supervised, it is necessary to define the transmission control panel
number in the TRANSMISSION CONTROL PANEL option (i.e. remote control panel directly
connected with the monitoring station through the RS-232 port);
-
in the remote control panel (option: CENTRAL MONITORING), declare from which control
panels in the network the monitoring is to be received in order to transmit it through the RS-
232 port directly to the monitoring station.
Recommendations regarding control panel operation in the network mode
-
network groups of control panels should coincide with the monitored groups of control
panels;
-
taking into account the system reaction time, each control station should be directly
connected with a monitoring station (only options - through the RS-232 port).
PORT TYPE: 3
- TELSAP 2100 monitoring
Facilitates operation of the monitoring station in a format identical to the basic digital monitoring
protocol of a TELSAP 2100 control panel.
Declared transmission bitrate: 2400 bps, 4800 bps.
PORT TYPE: 4
- TELSAP 2100 extended monitoring
Facilitates operation of the monitoring station in a format identical to the extended digital
monitoring protocol of a TELSAP 2100 control panel.
Declared transmission bitrate: 2400 bps, 4800 bps.
Note:
The TELSAP 2100 system digital monitoring may be implemented only from a local control panel. This
means that each control panel operating in the network may provide monitoring stations only with
information regarding events within the local detection area.