ID-E270-011GB
53
Variant 0
-
No EKS actuation criterion (output permanently deactivated).
Variant 1 – general 1
st
stage alarm
-
The output is activated in case a 1
st
stage alarm is generated in the control panel or in any
control panel from the common detection area.
Variant 2 – ‘union’ of 1
st
stage alarms in the assigned zones of the control panels from the common
detection area
-
the output is activated when a 1
st
stage alarm is generated in at least one of the zones
assigned to this relay.
Variant 3 – ‘conjunction’ of 1
st
stage alarms in the assigned zones of the control panels from the
common detection area
-
the output is activated when a 1
st
stage alarm is generated in at least two of the zones
assigned to this relay.
Variant 4 – general 2
nd
stage alarm
-
the output is activated in case a 2
nd
stage alarm is generated in the control panel or in any
control panel from the common detection area.
Variant 5 – ‘union’ of 2
nd
stage alarms in the assigned zones of the control panels from the
common detection area
-
the output is activated when a 2
nd
stage alarm is generated in at least one of the zones
assigned to this relay.
Variant 6 – ‘conjunction’ of 2
nd
stage alarms in the assigned zones of the control panels from the
common detection area
-
the output is activated when a 2
nd
stage alarm is generated in at least two of the zones
assigned to this relay.
Variant 7 – general fault in the control panel
-
the output is activated in case a general fault is detected in the control panel or in any
control panel from the common detection area.
Variant 8 – general non-maskable fault in the control panel
-
the output is activated in case a general non-maskable fault is detected in the control panel
or in any control panel from the common detection area.
Variant 9 – general technical alarm in the control panel
-
the output is activated in case a general technical alarm is generated in the control panel or
in any control panel from the common detection area.
Variant 10 – ‘union’ of faults in assigned EKS inputs
-
the output is activated in case a fault has occurred in at least one assigned input from the list
of assigned EKS elements. The assigned inputs may include own inputs of the controlled EKS
element. The list of assigned EKS inputs may include only their own control panel (when the
control panel operates in a network).
Variant 11 – ‘union’ of non-maskable faults in assigned EKS inputs