ID-E270-011GB
75
-
detection line earth fault;
-
number of line elements in a detection loop exceeding 127;
-
presence of not declared elements in a detection line;
-
incorrect parameters for the detection loop (resistance, capacity);
-
no response from a line element to a query from the control panel;
-
multiple declaration of the same line element.
4. Line element faults:
-
measuring element fault;
-
short circuit isolator actuated;
-
EEPROM memory fault;
-
EKS output line fault;
-
WE1 EKS input line fault;
-
WE2 EKS input line fault;
-
WE1 EKS non-maskable fault;
-
WE2 EKS non-maskable fault;
-
EWS relay fault;
-
battery of SAL external power adaptor fault.
5. Control panel input and output faults:
-
LS supervised potential outputs fault;
-
LK monitoring line outputs non-maskable fault.
6. Power supply fault:
-
voltage outage on the main power source;
-
reserve power supply fault (no battery, short circuit in terminals connecting the batteries or
B1 fuse damage);
-
decrease in battery voltage below 22 V ± 1 V;
-
battery cluster charger fault;
-
+ 5 V transducer fault (also a short circuit);
-
temperature probe fault (short circuit, no probe);
-
burnt or missing melt insert of the B2 fuse for the MZ-48 module;
-
earth fault, i.e. connection of the power supply output module with the control panel
housing or grounding.
7. Network faults:
-
hardware number not compliant with the declaration;
-
no network control panel declaration;
-
repeated control panel numbers in the network;
-
no. 1 ring fault;
-
no. 2 ring fault;
-
incorrect connection of rings;
-
no communication with the network control panel.
8. TSR-4000 terminal faults
-
configuration memory fault;
-
EPROM memory fault;
-
LCD display fault;
-
relay output fault;
-
signalling line fault;
-
incorrect terminal number;
-
230 V power supply fault;
-
battery fault;
-
battery charging system fault;