66
ID-E270-011GB
-
a logical number (1 ÷ 100);
Stage II:
UCS 6000 logical configuration consisting in:
-
declaring MGL modules;
-
declaring an MPD module;
-
declaring MPW modules;
-
defining the zone for the fire alarm generated by the MGS module;
-
MGL modules configuration:
•
defining the zone for the fire alarm generated by the MGL module;
•
defining the activation variant of an MGL module;
•
defining user messages for a technical alarm and non-maskable fault of an MGL
module output;
-
MPD module configuration:
•
defining activation variants for PK1, PK2 and an MPD module;
•
defining user messages for a technical alarm and non-maskable fault of PK1 and PK2
outputs of an MPD module;
-
MPW module configuration:
•
defining activation variants for PK1, PK2 and an MPW module;
•
defining user messages for a technical alarm and non-maskable fault of PK1 and PK2
outputs of an MPW module;
Variants of activating UCS 6000 control panel module outputs
See Table 7.6 for the possibilities of programming activation of UCS 6000 control panel module
outputs.
The "control panel number" parameter (only for control panels operating in a network) has the
following meaning:
control panel number = 0 shows the dependence on an event in any control panel included in the
common detection area;
control panel number > 0 shows the dependence on an event from a given control panel (provided it
is included in the common detection area);
control panel number ”―” allows for making actua]on dependent only on local control panel events.
For variants with additional zone dependencies: zone number = 0 shows the dependence on the total
number of events within all zones in a selected control panel included in the common detection area.
Table 7.6
Variant
Control
Panel
No.
Zone
number
Actuation Criterion
0
―
―
inactive output
1
0
―
general 1
st
stage alarm
2
0 ÷ 31
0 ÷ 1024 ‘union’ of 1
st
stage alarms in assigned zones