22
ID-E270-011GB
Line No.
Jumper
Jumper
position
Max. current
[mA]
Max. resistance
[Ω]
L3 (L7)
S23
1-2
1-2
2-3
20
22
50
2 x 100
2 x 75
2 x 45
L4 (L8)
S24
1-2
1-2
2-3
20
22
50
2 x 100
2 x 75
2 x 45
Note:
In case the ADC-4001 adapter with a grounded intrinsically safe barrier on a side line is used, the
earth fault signalling must be disconnected by the S4 jumper removal from the MSL-1M and MSL-2M
modules.
The MSL-XM module communicates with the PSC-49 module receiving information regarding the
current configuration of the addressable elements in the lines and commands to be executed
(actuate/dis-actuate an element, lines, reset an element, etc.) and returns processed data regarding
the addressable elements status and the detection line.