Maximum permissible resistance of detection line cabling
-
addressable line, depending on configuration
-
ADC-4001 side line
-
between two consecutive elements containing short circuit isolators
Maximum permissible capacity of an addressable detection line cabling
Minimum insulation resistance between cables in the installation
Addressable detection line operation layout:
-
loop-shaped – with a possibility to eliminate one break or short circuit in the
detection line cabling (A type detection line)
-
radial without a loop (B type detection line)
Number of addressable elements in one line, depending on the total quiescent
current but not higher than:
-
for A type lines
-
for B type lines
Maximum number of EKS-4001 monitoring and controlling elements connected to
a control panel
Maximum number of EWS-4001 multi-output controlling elements connected to
a control panel
Maximum number of EWS-4001 multi-output control elements connected to
one detection line
Maximum number of EWK-4001 multi-input monitoring elements connected to
a control panel
Maximum number of EWK-4001 multi-input monitoring elements connected to
one detection line
Maximum number of SAL-4001 acoustic signalling devices connected to
a control panel
Maximum number of UCS 4000 universal control panels connected to control panel
Maximum number of UCS 6000 universal control panels connected to control panel
Number of zones to which line elements are program assigned
Number of inter-dependent detector groups in a zone
2 x 100 Ω, 2 x 75 Ω
or 2 x 45 Ω
2 x 25 Ω
2 x 50 Ω
300 nF
100 kΩ
127
32
250
100
20
100
20
250
100
100
1024
1
(A and B)
Fire alarm types:
-
preliminary alarm
-
main alarm
Number of alarming variants to be used in zones
1
ST
STAGE ALARM
2
ND
STAGE ALARM