10 STANDARD CONFIGURATION
The POLON 4900 control panel delivered to a customer has manufacturer's pre-programmed
operation modes defined as the standard configuration.
According to the standard configuration, a control panel is programmed as follows:
-
the MSL-1M module is declared by default (all loop-shaped lines); MSL-2M and MSI-48
modules are not declared;
-
the control panel network number is set as 0 – individual control panel;
-
the control panel remote access is disabled;
-
every addressable element (in the address space) is declared as type 0 (not reviewed by the
control panel)
-
fire warning devices are potentially assigned to the zones with the numbers compliant with
the numbers of the lines in which they are installed (detectors – programmed as A group);
-
controlling, monitoring and signalling elements (EKS-4001, EWS-4001, EWK-4001, SAL-4001,
UCS 4000, UCS 6000) are not configured; line elements are not allocated, zones are not
assigned (zone matrix empty); no variants;
-
all user messages assigned to the EKS-4001, EWK-4001 logical numbers – standard;
-
fire extinguishing zones (1 ÷ 4) are assigned with variant 15 (two-stage alarm with
coincidence including two fire warning devices), other zones are assigned with variant 2
(two-stage alarm);
-
all user messages (technical alarms and non-maskable faults) are assigned to the logical
numbers of EKS-4001, EWK-4001 – of standard type;
-
variant 2 (two-stage alarming) is assigned to all zones,
-
all user messages assigned to zones – of standard type,
-
the PK1 relay (marked as PU) permanently programmed as a general fault signalling output;
-
the PK2 output relay programmed as TYPE 3 variant 1, without delays (actuation in the event
of a 1
st
stage alarm occurrence in the control panel);
-
the PK3 output relay programmed as TYPE 2 (monitoring output);
-
other relays (PK4 ÷ PK16) and signal lines (LS1 ÷ LS8) programmed as TYPE 0 (inactive);
-
the PK relays and LS signal lines potentially without zone interdependence (zone matrices
empty);
-
all LK monitoring lines programmed with variant 0 (inactive);
-
all user messages assigned to monitoring lines - standard;
-
DR-48 printer – not declared;
-
T1 time (for acknowledgement ) set at 30 seconds;
-
T2 time (for hazard recognition) set at 1 minute;
-
T3 time (alarm output actuation delay) set at 0;
-
times of automatic switching between the PERSONNEL PRESENT/PERSONNEL ABSENT
operation mode – not programmed;
-
default access code at the 2
nd
level – 2222;
-
default access code at the 3
rd
level – 3333;
-
default access code at the 4
th
level – 3112;
-
event memory cleared
-
review register cleared and the review monitoring function - inactive.