3101 111th Street SW
•
Suite F
•
Everett, WA 98204
425-353-7552
•
plcmultipoint.com
207
L
Re
v1
22
Gateway Commissioning & Start-up Guide
Assigning Light Nodes to a Zone
The next step in the process is to select which light nodes to include in the current zone.
The section at the bottom of the next screen features icons representing discovered lights
that are not already included in a zone, while the group on the top of the screen
represents those devices that have been sorted to include in the current zone.
The top section of the screen will be empty at the outset.
If all the devices visible in the bottom section of the screen are to be included in the current
zone, tapping “Select All” will move all icons from the lower section to the upper section.
If uncertain as to which of the lights displayed in the bottom section of the screen should
be included in the current zone, it will be necessary to identify the specific devices.
To do so, tap an individual light or switch icon in the bottom portion of the screen
to launch the identification screen.
When the identification screen first appears, the specific light associated with the icon
will begin to cycle on and off to provide a visual indication as to which device is represented.
The selected lights will continue to flash for approximately 10 seconds.
Tap the checkmark to include the device into the zone or tap the “X” to exclude a light
or switch from the zone.
Note:
Some light fixtures and LED drivers do not activate fast enough to flash for visual identification.
If this is encountered, listen carefully to hear the switching relay within the fixture adapter.
A mechanical switching sound will be heard latching on and off repeatedly during the 10 second
identification period.