
IB IL 24 PSDO 8-PAC
104 / 112
PHOENIX CONTACT
7619_en_05
D 4
Validation
Checklist for validating the safety module
Device type / Equipment identification
Version: HW/FW/FW
Date
Editor
Test engineer
Comment
No
.
Requirement (mandatory)
Yes
Comment
1
Have all the mandatory requirements for the "Planning" checklist been
met?
2
Have all the mandatory requirements for the "Assembly and electrical in-
stallation" checklist been met?
3
Have all the mandatory requirements for the "Startup and parameteriza-
tion" checklist been met?
4
Does the parameterization of the safe outputs correspond to the version
and the actual connection of the controlled devices?
5
Has the assignment of the actuators to the outputs and the variables of the
safe application program been tested (also as online status in
SafetyProg)?
6
Has a function test been performed to check all safety functions in which
the module is involved?
7
Have measures been taken to achieve a specific Cat.?
8
Do all cables correspond to the specifications?
9
Does the power supply correspond to the specifications for the protective
extra-low voltage in accordance with PELV?
10
Has the power supply of U
M
and U
S
in the Inline system from a power sup-
ply unit been implemented?
11
Is external protection of the module implemented (according to the speci-
fications in this user manual for supply voltage U
M
)?
12
INTERBUS-Safety: Is the shutdown time to be parameterized imple-
mented according to the planning? (Uniform shutdown time, derived from
the system specifications or shutdown time per channel)
13
Have measures been taken to prevent simple tampering?
14
Have measures been taken to prevent plugs being mixed up?
15
Are requirements for the actuators and cable installation observed accord-
ing to the SIL/SILCL/Cat./PL to be achieved?
16
Are the specifications for the parameterization for each channel imple-
mented?
17
Have test intervals been defined for testing the shutdown capability of the
actuators, if this is required to achieve a SIL/SILCL/Cat./PL?
18
For PROFIsafe: Is the F_iPar_CRC parameter greater than 0 for all de-
vices?
Содержание IB IL 24 PSDO 8-PAC
Страница 1: ...User manual IB IL 24 PSDO 8 PAC Inline module with safe digital outputs...
Страница 16: ...IB IL 24 PSDO 8 PAC 16 112 PHOENIX CONTACT 7619_en_05...
Страница 32: ...IB IL 24 PSDO 8 PAC 32 112 PHOENIX CONTACT 7619_en_05...
Страница 38: ...IB IL 24 PSDO 8 PAC 38 112 PHOENIX CONTACT 7619_en_05...
Страница 54: ...IB IL 24 PSDO 8 PAC 54 112 PHOENIX CONTACT 7619_en_05...
Страница 68: ...IB IL 24 PSDO 8 PAC 68 112 PHOENIX CONTACT 7619_en_05...
Страница 78: ...IB IL 24 PSDO 8 PAC 78 112 PHOENIX CONTACT 7619_en_05...
Страница 80: ...IB IL 24 PSDO 8 PAC 80 112 PHOENIX CONTACT 7619_en_05...
Страница 90: ...IB IL 24 PSDO 8 PAC 90 112 PHOENIX CONTACT 7619_en_05...
Страница 106: ...IB IL 24 PSDO 8 PAC 106 112 PHOENIX CONTACT 7619_en_05...