Connection examples for safe outputs
7619_en_05
PHOENIX CONTACT
6.3
Measures required to achieve a specific safety in-
tegrity level
The safety integrity (SIL, SILCL, performance level, and category) that can be achieved is
specified for each connection example.
SIL, SILCL
When the SIL/SILCL is specified, the module takes up 1% of the specified SIL/SILCL.
Performance level
Category
In order to actually achieve the specified category, the required measures listed below must
be implemented.
Cat. 2
–
Use proven safety principles.
–
Use appropriately qualified actuators (see Section “Requirements for controlled devic-
–
Please note that mechanical failure of the switching device can result in the loss of the
safety function.
–
Prevent the welding of contacts on the connected contactors or safety relays with ap-
propriate protection against overcurrent and surge voltage.
–
Please note that
a single
error can result in the loss of the safety function between tests.
–
Make sure that the external wiring is tested by the machine control system on machine
startup and at suitable intervals. This test must detect the loss of the safety function.
–
In the event of an error, either safe disconnection must be implemented or a warning
(optical and/or audible) must be generated depending on the application.
In order to determine the probability of failure according to EN 61508 (SIL), use the spec-
ifications from the INTERBUS-Safety system user manual or the standard.
In order to determine the probability of failure according to EN 62061 (SILCL), use this
standard.
Table 6-3
PFD and PFH depending on the SIL/SILCL
PFD
PFH
SIL 2/SILCL 2
1% of 10
-2
1% of 10
-6
SIL 3/SILCL 3
1% of 10
-3
1% of 10
-7
Use standard EN ISO 13849-1 to determine the performance level.
Содержание IB IL 24 PSDO 8-PAC
Страница 1: ...User manual IB IL 24 PSDO 8 PAC Inline module with safe digital outputs...
Страница 16: ...IB IL 24 PSDO 8 PAC 16 112 PHOENIX CONTACT 7619_en_05...
Страница 32: ...IB IL 24 PSDO 8 PAC 32 112 PHOENIX CONTACT 7619_en_05...
Страница 38: ...IB IL 24 PSDO 8 PAC 38 112 PHOENIX CONTACT 7619_en_05...
Страница 54: ...IB IL 24 PSDO 8 PAC 54 112 PHOENIX CONTACT 7619_en_05...
Страница 68: ...IB IL 24 PSDO 8 PAC 68 112 PHOENIX CONTACT 7619_en_05...
Страница 78: ...IB IL 24 PSDO 8 PAC 78 112 PHOENIX CONTACT 7619_en_05...
Страница 80: ...IB IL 24 PSDO 8 PAC 80 112 PHOENIX CONTACT 7619_en_05...
Страница 90: ...IB IL 24 PSDO 8 PAC 90 112 PHOENIX CONTACT 7619_en_05...
Страница 106: ...IB IL 24 PSDO 8 PAC 106 112 PHOENIX CONTACT 7619_en_05...