Parameterization of the safety module
7619_en_05
PHOENIX CONTACT
5.5
Behavior of the outputs in the event of enabled
switch-off delay for stop category 1
Depending on the event that causes the outputs to be switched off, the parameterization of
the switch-off delay, and also on the parameterization of the shutdown time in the case of
INTERBUS-Safety, the time until the outputs are actually switched off can vary.
For the switch-off operation, please take into consideration the following:
–
The switch-off operation can be interrupted by switching the output on again.
–
If the parameterization of the module is modified, the modified parameterization does
not take effect until all the outputs have been switched off.
If the parameterization is modified before the switch-off operation is complete, diagnos-
tic message 02F2
hex
is generated.
–
Carry out a validation every time the parameterization is modified.
–
Please note that when the parameterization is modified, this can result in delayed start-
up due to the switch-off delay time.
Table 5-2
Switching off the outputs according to the trigger event and the parameterization
Switching off outputs
Influence of parameterized
Switching off outputs
Switch-off
delay
Shutdown
time
–
By the safe controller
Yes
No
Once the parameterized switch-off delay
has elapsed
–
After a bus error
Yes
Yes
After the sum of the parameterized
shutdown time + the parameterized
switch-off delay has elapsed
–
After a short circuit, cross-circuit, fail-
ure of the supply voltage, or hardware
fault
No
No
Immediately (only stop category 0)
WARNING: Delayed shutdown when using stop category 1
For stop category 1 please take into consideration the following:
–
If the parameterized shutdown time is exceeded, the affected outputs are only set to
the safe state once the switch-off delay has elapsed.
–
In the event of an error (excluding bus errors) the affected outputs are switched off
immediately (without delay). In this case, only stop category 0 is supported.
WARNING: Incorrect design of safety distances due to incorrect calculation of the
overall shutdown time
When designing the safety distances, please take into consideration the following:
The overall shutdown time of the outputs is calculated as the sum of the parameterized
shutdown time and the parameterized switch-off delay time.
Содержание IB IL 24 PSDO 8-PAC
Страница 1: ...User manual IB IL 24 PSDO 8 PAC Inline module with safe digital outputs...
Страница 16: ...IB IL 24 PSDO 8 PAC 16 112 PHOENIX CONTACT 7619_en_05...
Страница 32: ...IB IL 24 PSDO 8 PAC 32 112 PHOENIX CONTACT 7619_en_05...
Страница 38: ...IB IL 24 PSDO 8 PAC 38 112 PHOENIX CONTACT 7619_en_05...
Страница 54: ...IB IL 24 PSDO 8 PAC 54 112 PHOENIX CONTACT 7619_en_05...
Страница 68: ...IB IL 24 PSDO 8 PAC 68 112 PHOENIX CONTACT 7619_en_05...
Страница 78: ...IB IL 24 PSDO 8 PAC 78 112 PHOENIX CONTACT 7619_en_05...
Страница 80: ...IB IL 24 PSDO 8 PAC 80 112 PHOENIX CONTACT 7619_en_05...
Страница 90: ...IB IL 24 PSDO 8 PAC 90 112 PHOENIX CONTACT 7619_en_05...
Страница 106: ...IB IL 24 PSDO 8 PAC 106 112 PHOENIX CONTACT 7619_en_05...