Application manual for PSRclassic and PSRmultifunction, and the modular safety relay system
PHOENIX CONTACT
102597_en_03
5.3.1
PSR-ESA4/2x1/1x2 up to PL e/SIL 3
Two-channel safety door monitoring with automatic reset (with cross-circuit
detection)
Application example
–
Two-channel safety door monitoring with two position switches
–
Cross-circuit detection
–
Ground fault detection (S11, S12 only)
–
Automatic reset (bridge S33, S34)
–
Feedback of contactor contacts K3 and K4 at S33 and S34
–
Stop category 0
–
Monitoring of external contactors
–
Safety level of the example up to PL e (EN ISO 13849-1) and SIL 3 (EN 62061)
Figure 5-13
Two-channel safety door monitoring with automatic reset
PSR-ESA4/2x1/1x2
Order No.
2963750 with screw connection
2963938 with spring-cage connection
Technical data
–
24 V AC/DC
–
2 enabling current paths, 1 signaling current path
–
Manual start or autostart
–
Reinforced insulation
–
Cat. 4/PLe in accordance with EN ISO 13849-1, SILCL 3 in
accordance with EN 62061