Application examples for conventional PSRclassic safety relays
102597_en_03
PHOENIX CONTACT
Function description
For additional diagnostic descriptions, please refer to Section 8.
Notes on theapplication
example
1.
The emergency stop control device is positive opening in accordance with EN 60947-5-1.
2.
Contactors K3, K4, K5, and K6 have mirror contacts in accordance with EN 60947-4-1.
3.
Stop category 0 describes an immediate stop by removal of power by interrupting a
machine or drive element in accordance with EN 60204-1.
4.
Install the safety relay and contactors together in an installation space in accordance
with EN 60204-1 (e.g., in the control cabinet). This prevents a cross-circuit at the output
of the safety relay.
5.
When using the safety relay, take into consideration the maximum permissible number
of cycles for observing the SIL/PL safety characteristics in the specific application. The
safety characteristics can be found in the AH EN SAFETY CHARACTERISTICS appli-
cation note or the SISTEMA library.
Start
Action
Result
Diagnostics
1.
Unlock emergency stop
button S1.
The emergency stop button closes enable circuit S11, S12
and S21, S22 of the safety relay.
The circuit is enabled via the reset button.
2.
Press reset button S2.
Contactors K3 … K6 are activated and the mirror contacts
(N/C contacts of K3 … K6) in the reset circuit are opened.
Stop
Action
Result
Diagnostics
1.
Press emergency stop
button S1.
The safety function is triggered and contactors K3 … K6
drop out.
In the reset circuit, the mirror contacts of K3 … K6 are
closed.
Power
IN1/2
K1
K2
Power
IN1/2
K1
K2
Power
IN1/2
K1
K2
Содержание 2702924
Страница 137: ......