Application examples for conventional PSRclassic safety relays
102597_en_03
PHOENIX CONTACT
Function description
For additional diagnostic descriptions, please refer to Section 8.
Notes on theapplication
example
1.
When using safety hinge switches, observe the notes in standards EN 953, EN 1088,
EN ISO 13857, and EN ISO 14119.
2.
Contactors K3 and K4 have mirror contacts in accordance with EN 60947-4-1.
3.
Stop category 0 describes an immediate stop by removal of power by interrupting a
machine or drive element in accordance with EN 60204-1.
4.
Install the safety relay and contactors together in an installation space in accordance
with EN 60204-1 (e.g., in the control cabinet). This prevents a cross-circuit at the output
of the safety relay.
5.
When using the safety relay, take into consideration the maximum permissible number
of cycles for observing the SIL/PL safety characteristics in the specific application. The
safety characteristics can be found in the AH EN SAFETY CHARACTERISTICS appli-
cation note or the SISTEMA library.
Start
Action
Result
Diagnostics
1.
Close the safety door.
The safety door circuit closes enable circuit S11, S12 and
S21, S22 of the safety relay.
The circuit is enabled via the reset button.
2.
Press reset button S2.
Contactors K3 and K4 are activated and the mirror contacts
(N/C contacts of K3 and K4) in the reset circuit are opened.
Stop
Action
Result
Diagnostics
1.
Open the safety door.
The safety function is triggered and contactors K3 and K4
drop out.
In the reset circuit, the mirror contacts of K3 and K4 are
closed.
Power
IN1/2
K1
K2
Power
IN1/2
K1
K2
Power
IN1/2
K1
K2
Содержание 2702924
Страница 137: ......