Safety technology basics
102597_en_03
PHOENIX CONTACT
Example
For an emergency stop application with the PSR-ESAM4 (see
culations can be made:
Assumed values
Cable cross section: A = 1.5 mm²
Electrical conductivity of copper (Cu):
= 56 m/(
x mm²) (at 20 °C)
Technical data for the
safety relay
Input data:
Maximum voltage drop for S11-S12, S21-S22, and S33-S34: approximately 2 V DC (corre-
sponds to approximately 50
= RL)
RL = R1 + R2 + R3
RL = 50
Calculated value
l = RL x A x
l = 50
x 1.5 mm² x 56 m/(
x mm²)
l = 4200 m
Where:
This refers to the forward and return line for both channels in the enable circuit and reset
circuit (S11-S12, S21-S22, and S12-S34).
The specified values can be found in the data sheet for the corresponding safety relay.
l
Permissible cable length
R
L
Cable resistance
A
Cable cross section
(Kappa)
Electrical conductivity of copper (Cu)
If the application is operated with autostart, the cable lengths between S12-S35 can be
disregarded.