Data message format
3785_en_B
PHOENIX CONTACT
71
5.4.9.3
Instance definitions for four-port devices (GW.../4DB9)
Input assembly instances:
Input assembly instances are grouped into one continuous
array between the instances. One or more input instances may be read with one I/O
connection. For example, if addressing instance 101, all input instances for both serial and
socket data, 101, 102, 103, 104, 105, 106, 107, and 108, may be read in one connection.
The length of the read (input) connection may range from 1 to the total length for all input
instances. Multiple controllers may access the input assembly instances simultaneously.
Table 5-40
Output assembly instance attributes
Assembly
instance number
Name
Data type
Data value
Access rule
109
Transmit data to serial
ports 1 to 2
Transmit data to socket
ports 1 to 2
BYTE array length = (4 +
maximum RX packet size)
0 - 255
Set
110
Transmit data to serial
port 2
Transmit data to socket
ports 1 to 2
BYTE array length = (4 +
maximum RX packet size)
0 - 255
Set
113
Transmit data to socket
ports 1 to 2
BYTE array length = (4 +
maximum RX packet size)
0 - 255
Set
114
Transmit data to socket
port 2
BYTE array length = (4 +
maximum RX packet size)
0 - 255
Set
Table 5-41
Input assembly instance attributes
Assembly
instance number
Name
Data type
Data value
Access rule
101
Receive data from serial
port 1
BYTE array length = (4 +
maximum RX packet size)
0 - 255
Get
102
Receive data from serial
port 2
BYTE array length = (4 +
maximum RX packet size)
0 - 255
Get
103
Receive data from serial
port 3
BYTE array length = (4 +
maximum RX packet size)
0 - 255
Get
104
Receive data from serial
port 4
BYTE array length = (4 +
maximum RX packet size)
0 - 255
Get
105
Receive data from socket
port 1
BYTE array length = (4 +
maximum RX packet size)
0 - 255
Get
106
Receive data from socket
port 2
BYTE array length = (4 +
maximum RX packet size)
0 - 255
Get
107
Receive data from socket
port 3
BYTE array length = (4 +
maximum RX packet size)
0 - 255
Get
108
Receive data from socket
port 4
BYTE array length = (4 +
maximum RX packet size)
0 - 255
Get
Содержание 2702772
Страница 1: ...User manual UM EN GW EIP ASCII Protocol converter for ASCII to EtherNet IP...
Страница 6: ...GW EIP ASCII 4 PHOENIX CONTACT 3785_en_B...
Страница 14: ...GW EIP ASCII 12 PHOENIX CONTACT 3785_en_B...
Страница 52: ...GW EIP ASCII 50 PHOENIX CONTACT 3785_en_B...
Страница 82: ...GW EIP ASCII 80 PHOENIX CONTACT 3785_en_B...