Configuration and startup
3785_en_B
PHOENIX CONTACT
41
4.9.2
PLC interface
The “PLC Interface” page provides diagnostic information about the EtherNet/IP
communication to a PLC. The values can be reset to zero at any time by clicking the “Reset
Statistics” button.
Figure 4-19
“PLC Interface” page
Active session count:
Displays the number of active EtherNet/IP sessions. Sessions
support both Class 1 I/O and Class 3 messages, and may be initiated or terminated by the
PLC or the GW EIP/ASCII....
Active connections:
Displays the current number of Class 1 and Class 3 active
connections.
Total connections established:
Displays the total number of established connections.
Connections timed out:
Displays the number of connections that have closed due to a
time out.
Connections closed:
Displays the number connections that have closed due to a standard
processes.
Class 3 messages/responses received:
Displays the number of Class 3 messages and
responses received from the PLCs.
Broadcast messages received:
Displays the number of broadcast messages received
from the PLCs.
Class 3 messages/responses transmitted:
Displays the number of Class 3 messages
and responses sent to the PLCs.
Class 1 output updates from PLC:
Displays the number of Class 1 output data updates
received from the PLCs.
Class 1 input updates to PLC:
Displays the number of Class 1 input data updates sent to
the PLCs.
Содержание 2702772
Страница 1: ...User manual UM EN GW EIP ASCII Protocol converter for ASCII to EtherNet IP...
Страница 6: ...GW EIP ASCII 4 PHOENIX CONTACT 3785_en_B...
Страница 14: ...GW EIP ASCII 12 PHOENIX CONTACT 3785_en_B...
Страница 52: ...GW EIP ASCII 50 PHOENIX CONTACT 3785_en_B...
Страница 82: ...GW EIP ASCII 80 PHOENIX CONTACT 3785_en_B...